VITALink® 2 Hour Fire Resistive CIC/CI (Unshielded)

VITALink® is a registered trademark of RSCC Wire & Cable, LLC, a Marmon Wire & Cable/Berkshire Hathaway Company.

VITALink® 2 Hour Fire Resistive CIC/CI Unshielded

Construction:

  • Conductors: 12-18 AWG Solid Copper or Stranded Copper specially engineered to minimize embrittlement due to fire exposure
  • Tape: Flame Retardant Tape
  • Insulation: Low Smoke, Zero Halogen Thermoset Fire-Roc™
  • Core Assembly: Color Coded Insulated Conductors of Red and Black
  • Jacket: Red Low Smoke, Zero Halogen Polyolefin (Sequential Footage Marker Provided Every Two Feet)

Applications:

  • Emergency Voice/Alarm Communication Smoke and Fire Alarm Systems
  • Fireman’s Telephone and Area of Refuge Communication Systems
  • Visible Notification Appliances

35777, 36337, 36341, 36338, 36340, 36342, 36339

 

Part Numbers & Specs

SpecPart NumberNo. of ConductorsAWGSolid or Stranded Copper ConductorsNominal Diameter (inches)Nominal Weight (lbs./1000 ft.)Nominal Capacitance (pF/ft.) 
Spec36337218Solid.3054117
Spec35777216Solid.3215219
Spec36341*216Stranded.3445419
Spec36338214Solid.3526120
Spec36340*214Stranded.3686520
Spec36342*212Solid .4029022
Spec36339*212Stranded.4169222
*Non-stock item. Lead time and MOQ may be required.

Notes:

  • Refer to Specs above for hardware certifications
  • Refer to R27557 Fire Resistive Cable (UL)
  • VITALink® Brand Type FPLR-CI-LS, CMR-CI-LS, & PLTC-CI-LS for use in System No. FHIT.40A and FHITC.40A when installed in accordance with the manufacturer’s installation instructions dated May 2017 for use as CIC cable.
  • For use as CI cable when installed per the NEC and local code. For vertical installation lengths beyond 30 ft. (18 AWG) or 45 ft. (12-16 AWG) cables are to be supported using a stainless steel wire mesh.
  • Authorities having jurisdiction should be consulted before installation.

Compliance:

  • NEC Type FPLR-CI-LS, CMR-CI-LS, and PLTC-CI-LS for use in Electrical Circuit Integrity System FHIT 40A
  • c(UL) Listed CMR-LS
  • CEC and CSA listed FAS 90 to C22.2 No. 208-14
  • UL Certified to ANSI / UL 2196 2-Hour fire rating for use in FHIT system 40A. (See UL Fire Resistance Directory R27557)
  • CAN / ULC-S139 Certified with Hose Stream Test for use in FHITC system 40A
  • UL 1424 Listed FPLR-CI-LS for Power-Limited Fire Alarm Cables; 300V / 105°C
  • UL 13 Listed PLTC-CI-LS for Power-Limited Circuit Cables; 300V / 105°C
  • UL 444 Listed CMR-CI-LS for Communication Cable; 300V / 105°C
  • Fire certified for power-limited system use at 72V phase-to-phase utilization voltage
  • Sunlight Resistant
  • For use in wet locations
  • NYC Electrical Advisory Board approval # 54502, April 2017
  • California State Fire Marshal Approved