COM-Link® Category 5e 350 MHz UTP – Riser

COM-Link Category 5e 350 MHz UTP - RiserDiagram of COM-Link Category 5e 350 MHz UTP - Riser

Construction:

  • Conductors: 24 AWG Solid Bare Copper
  • Cable Assembly: 4 Pairs Cabled Together

Insulation: Polyethylene

Jacket: FR-PVC

Compliance:

  • ETL Verified ANSI/TIA-568-C.2 (Cat 5e)
  • UL Subject 444 Communications Cables
  • UL Listed Type CMR
  • UL 1666 Riser Flame Test
  • NEC Article 800
  • c(UL) Type CMR
  • ICEA S-80-576
  • California State Fire Marshal
  • RoHS Compliant

Applications:

  • Gigabit Ethernet (1000Base-T)
  • Multimedia and ISDN
  • High-Speed Voice/Data Applications
  • 1.2 Gbps Ethernet
  • Broadband Video
  • Desktop Publishing

32881, 32882, 32883

 

Part Numbers & Available Put Ups

SpecPart NumberJacket Color1,000' Box1,000' ReelBulk Reels
Spec32883BLUEXXX
Spec32882GRAYXXX
Spec32881WHITEXXX

Physical Data

SpecificationValue
Nominal Cable Diameter (inches)0.175
Nominal Cable Weight (lbs./1,000 ft.)18.0
Installation Temperature Rating (Celsius)0 to +60
Operation Temperature Rating (Celsius)-20 to +75
Pulling Force (Max lbs.)25.0

Transmission Throughput

Char. Impedance Freq. (MHz)Char. Impedance (Ohms) (+/-15)Return Loss (dB) (Min.)Attenuation dB / 100m (Max.)NEXT dB / 100m (Min.)PSNEXT dB / 100m (Min.)ACRF dB / 100m (Min.)PSACRF dB / 100m (Min.)
110020265.362.363.860.8
4100234.156.353.351.748.7
810024.55.851.848.845.742.7
10100256.550.347.343.840.8
16100258.247.344.339.736.7
20100259.345.842.837.734.7
2510024.310.444.341.335.832.8
31.2510023.611.742.939.933.930.9
62.510021.51738.435.427.824.8
10010020.12235.332.323.820.8
2001001832.430.827.82014.7
35010016.344.827.524.2179.9