COM-Link® Category 6A UTP – Riser

Diagram of Cat 6A UTP CMR Diagram

Construction:

  • Conductors: 23 AWG Solid Bare Copper
  • Cable Assembly: 4 Pairs Cabled Together with X-Web

Insulation: Polyethylene Nom Diameter 0.0435"

Tape 1: Polyester

Tape 2: Non-Conductive Tape Technology

Jacket:

  • PVC

Compliance:

  • UL Subject 444 Communications Cables
  • UL Listed Type CMR
  • UL 1666 Riser Flame Test
  • NEC Article 800
  • c(UL) Type CMR
  • California State Fire Marshal
  • RoHS Compliant

Applications:

  • Gigabit Ethernet (10GBase-T, 1000Base-T, 10Base-T)
  • Multimedia and ISDN
  • High-Speed Voice/Data Applications
  • 1.2 Gbps Ethernet
  • Broadband & Digital Video
  • Desktop Publishing

36508, 36509, 36599

Part Numbers & Available Put Ups

SpecPart NumberJacket Color1,000' Reel
Spec36508BLUEX
Spec36509WHITEX
Spec36599GRAYX

Physical Data

SpecificationValue
Nominal Cable Diameter (inches)0.275
Nominal Cable Weight (lbs./1,000 ft.)32.0
Installation Temperature Rating (Celsius)0 to +60
Operation Temperature Rating (Celsius) -20 to +75

Transmission Throughput

Char. Impedance Freq. (MHz)Char. Impedance (Ohms) (+/-15)Return Loss (dB) (Min.)Attenuation dB / 100m (Max.)NEXT dB / 100m (Min.)PSNEXT dB / 100m (Min.)ACRF dB / 100m (Min.)PSACRF dB / 100m (Min.)
110020274.372.367.864.8
4100233.865.363.355.852.8
810024.55.360.858.849.746.7
1010025659.357.347.844.8
16100257.556.254.243.740.7
20100258.454.852.841.838.8
2510024.39.453.351.339.836.8
31.2510023.610.551.949.937.934.9
62.510021.51547.445.431.928.9
10010020.119.144.342.327.824.8
20010018.027.639.837.821.818.8
25010017.331.138.336.319.816.8
30010016.834.337.135.118.315.3
40010015.94035.333.315.812.8
50010015.245.333.831.813.810.8